Select an occupancy containing significant quantities of fire detection and protection equipment. Typically, public assembly bu
Select an occupancy containing significant quantities of fire detection and protection equipment. Typically, public assembly buildings contain such equipment in sufficient quantities. If you select a large, campus-type occupancy, choose one of the larger buildings but be sure to write of the overall campus system as systems and or part of the systems will be shared. You will need to contact an owner, maintenance person or other responsible party that can give you access to all the systems.
Warning:
You may want to confirm your choice with the instructor prior to getting heavily involved in the project.
A written Report will be submitted to the Canvas upload: Due (See Unit 16 in the Modules). Submit them in MS Word .doc or .docx format.
Length
Your report should be written in a simple report format in 8-1/2 X 11
format.
The text length must be at least 800 words, double-spaced and includes photos and or diagrams of the items you are writing about. (approximately three written pages and a cover page – with photos and diagrams there will many more pages). Depending on how you write you may need to write more than 800 words to make your report interesting and convey your thoughts.
Use 12-point font with all margins set at one inch. If you cannot find enough information let me know so I can offer some advice.
Content
A simple rule to follow regarding the content of the report: If the textbook mentions it and the occupancy has it, it needs to be included:
The text of the report should contain general information about the occupancy and all specifics of the fire detection and suppression equipment on site. You can also make the report interesting by provide other construction or features related to fire and life safety. Select a building with significant fire detection and suppression equipment and explain why you chose that particular building.
DO include images of the systems you are writing about.
Diagrams & Photographs
Diagrams and/or photographs shall be provided to amplify points made in the text of the report. Include a drawing of the campus indicating locations of outdoor fire protection equipment, fire department accesses, and the municipal water system. The location of all of the interior fire detection and suppression equipment must also be included.
Summary Page
A closing summary paragraph(s) should also be included.
MEASURED COMPONENTS
The overall grade for the term project will be based on the following elements presented in the written report and class presentation:
1. Initiative: Did the student actively seek out an occupancy and make contact with the appropriate responsible person to provide them access?
2. Organization: Did the narrative text flow in a logical progression? Was the overall document organized according to the INSTRUCTIONS?
3. Appearance: Was the report completed in 8-1/2 x 11 inch format using the proper margins, 12-point font, and double-spaced? Was at least 800 words without including redundancy?
4. Introduction: Was there a short introductory paragraph and was it interesting and accurate?
5. Spelling/grammar: Was there an absence of spelling and grammar errors?
6. Identification of key elements: Were all of the fire protection elements identified and described accurately?
7. Terminology: Were the proper terms used to describe fire protection elements?
8. Use of visual aids: Were images, photographs and/or diagrams used to convey the idea or concept?
9. Summary: Was there a short closing summary paragraph and was it accurate?
10. Overall report: Was the overall report informative and educational illustrating salient points?
Sonoma Veterans War Memorial Building
126 First Street West
Sonoma, CA 95476
(707)938-4105
Fire 74: Fire Protection and Suppression Systems
April 14, 2010
Team Gold Star
Kyle Jordan
Domanic Marks
Samuel Munguia
The Sonoma Veterans Memorial Building is one of eight Sonoma County owned and
operated buildings that are dedicated to a public purpose in the memory of the men and women
who have defended our nation. The role of fire protection equipment and systems is to
contain/control fires before they get large and cause loss of life and property. In this report we
will be exploring the fire protection systems for this building because we recognize that the
safety of human lives, property and long-term profitability of the Sonoma Veterans Memorial
building all hinges on their quality.
This Veterans facility is located two blocks from the historic Sonoma plaza at 126 First
Street West in the city of Sonoma, California. Designed by architect J. Clarence Felciano this
16,200 square feet building was built in 1952 and is now over forty-eight years old. The
building site sits on 10.2 acres, the largest of the eight memorial locations in Sonoma County,
and is adjacent to a Memorial Cemetery. See diagram D-1 for building floor plan.
General Building Description and Purpose
The Sonoma Veterans Memorial Hall is a spacious single story commercial facility with
concrete walls and wood frame construction. As defined by the California Building Code this
building is an A2 classification. Structural highlights include bowstring trusses in the auditorium
and a roof is comprised of diagonal sheathing over wood joists.
This building was structurally evaluated in February of 1991 and seismic retrofitting was
done. In May of 1991 seismic retrofit was completed and columns hold downs, and sheer walls
were all added into place. The building was also retrofitted with an automatic sprinkler system in
January of 1996 and a new roof was installed in the summer of 1996. In September of 1997 steel
beams were added under the wood trusses and steel columns were added to support the overall
structure of the building.
The building features a spacious carpeted lobby, large 80’ x 55’ auditorium with
hardwood floors, a retractable theater style seating system and theatrical stage with full lighting
capabilities. The building is equipped with a full commercial kitchen featuring a pass through
counter to the 63’ x 33’ dining room. There is also a 45’ x 19’ lounge room, office area, shop
room, restroom and shower facilities and ample storage space. See diagram D-2 for specific
building occupancy standards.
This dedicated memorial is used for meetings, events and ceremonies by the veterans and
public year round and has been identified as an emergency shelter, disaster response and post
disaster recovery location if needed.
Operation and Maintenance Responsibilities
Responsibility for operating this building transferred to the Regional Parks Department in
1978 and since then its use and operation have been managed by the Regional Parks Department,
which handles all the marketing, booking and collection of rental fees. In the mid 1990’s,
building maintenance responsibility was transferred to the Facilities Operations Division of the
General Services Department. The grounds are maintained by Regional Parks. Capital projects
are managed by the General Services Architecture Division and funded through the Capital
Project Budget, with most of the capital funding coming from the County’s General Fund.
Fire and Life Safety Overview
The faster the building occupant and fire service personnel can respond, enter, locate the
incident, and safely operate in a building, the sooner they can mitigate an incident in a safe
manner for themselves as well as occupants. Fire protection systems and equipment are installed
in buildings to protect employees, the public, the property and the firefighters that will respond
to an emergency. Like most other types of equipment, fire protection systems and life safety
equipment need periodic inspection, testing and maintenance to ensure reliability.
The building is equipped with fire extinguishers with classifications that are appropriate
for their location. The kitchen is equipped with a Wet Chemical Extinguishing System over the
gas range. There is a fire alarm panel with detectors that are monitored by the local Sonoma Fire
District. There are fire sprinklers throughout the Dining room, Lobby, Lounge, Auditorium and
stage area. The buildings Auxiliary services also mitigate the dangers. See diagram D-3 for Fire
and Emergency equipment plan.
Sprinkler System
The NFPA standard 13 addresses the installation and design of commercial sprinklers.
The wet pipe sprinkler system in this building consists of 2 ½ inch steel piping. A wet pipe
sprinkler system consists of water already in the piping ready to suppress in the event of a fire.
The sprinkler system runs throughout the entire building and can flow roughly 20-40 gallons of
water per minute. The system is fed by one of the two 5 inch underground water lines. The
underground lines are estimated to have 65-85 psi of residual pressure.
There are also sprinklers that run both above the stage and underneath it for added
suppression. Another unique location for the sprinklers is under the eaves and over hang on the
outside of the building. The sprinkler system is automatic and requires no human interaction.
The system activates when the sprinkler heads are exposed to extreme heat, inside the glass bulb
is a liquid that expands when exposed to heat, when the liquid expands the glass breaks. The
sprinklers in the building are classified as ordinary with a temp range of 135-175 degrees F.
There are different heads with different liquids that expand at different rates in the frangible
glass bulbs according to heat temperature. These frangible bulbs are identified by different color
liquids that represent the temperature ranges. The sprinkler heads/ nozzles are strategically
placed to spray large amounts of water on a potential fire. Only the heads exposed to the heat
will activate. There are different designs of heads in the building specifically engineered to work
different. When activated, the system will run until turned off by the fire department.
Replacement heads are required and they can be found in the building by the riser. It is very
important that when a sprinkler head needs to be replaced that it is replaced with the same type
of head so this facility has replacements on hand for that very reason.
The components of a sprinkler system consist of piping, sprinkler heads, valves, and Fire
department connections (FDC). Each sprinkler system includes a water supply main which is the
piping that connects the sprinkler system to the main water supply (the underground municipal
main). System Risers extend vertically from the water supply to feed the cross or feed mains.
Feed mains are piping that supplies water to the cross mains. Branch lines are pipes that contain
the individual sprinkler heads. The fire department connection is located on the outside of the
building. This Connection is used to augment the water supply and pressurize the system. The
fire dept connects and pumps water into the system, this connection is above the water supply
valve. The FDC connects to the riser above the check valve. The piping is set up in this manner
so that even if the OS&Y are shut the fire dept can still get water to the sprinkler system through
the FDC. The buildings FDC are 4 inch piping with 2 ½ inch connections.
Many municipal, government and health department buildings require a back flow
prevention device between the public water main and the automatic fire sprinkler system. The
Sonoma Veterans building has two back flow devices that for extra protection. Any FDC must be
situated between the backflow prevention device and the sprinkler riser. Tamper monitors are
located on the OS&Y valve which will alert those monitoring off premises that there is a
problem. A water flow indicator is located on the riser this indicator will sound an alarm when
water is flowing. The flow indicator consists of a paddle that protrudes through the riser into the
water way. Movement of the paddle sounds an alarm. The paddle is thin and pliable so as not to
obstruct the water flow. The 1987 insurance services report that sprinkler system controlled 98%
of fires. These sprinklers systems are not tested by the fire department but by certified licensed
technicians every five years. The NFPA standard 25 addresses the inspection, testing, and
maintenance on the sprinkler systems.
Suppression System
The Wet Chemical Extinguishing system in the kitchen is a pre-engineered system. The
following components makeup the system: storage tank for the expellant gas and agent, Piping to
carry the gas and agent, Nozzles for dispersal of the agent, and actuating mechanism. This
system is designed to activate when the fusible link in the hood and duct system melts in
response to heat. The fusible link triggers a mechanical release that starts the flow of expellant
gas and agent. This system can also be manually activated from a pull station. This system is
inspected monthly by Sonoma County’s FAC OPS division. If the Wet Chemical system were to
be activated and the agent discharged, the kitchen would not be allowed to be operational until
the health department does there inspection.
Fire Control Panel
The Fire Alarm control panel at this location is what contains the controls, relays,
switches and necessary circuits to furnish power to a fire detection system, and receive sig nals
from detection devices and then transmit them to signaling devices and auxiliary equipment. This
control panel runs on normal AC power but also has a 24-volt standby battery, and an emergency
generator. Because the fire detection system must be able to perform in an emergency without
failure, the control panel is required to provide a trouble signal in the event of a power failure, an
open circuit or a ground fault. It should give an audible or visual trouble signal on the panel.
Another function of the control panel is accepting a signal from the detection device and
triggering the various audible devices and auxiliary devices such as fire doors, fan shut-offs, and
multiple other things. The control panel will also provide test switches, as well as co ntrol
switches for testing lamps, drills, etc. There will also be switches to silence the alarms, reset the
system, or disconnect certain circuits.
The detection systems at this facility can be activated manually, and automatically. The
manual activations consist of single-action and double-action pull stations. A double-action pull
station means you have to push in, to expose the pull-down lever. These are near major exits and
also spaced through corridors. This building also has thermal heat detectors, which are mostly
rate of rise detectors in that they activate when it detects an abnormally high air temperature.
Heat detectors are the cheapest form of detection device but are suited mainly for smaller,
enclosed areas. In addition to the heat detectors, we also have both types of smoke detectors,
ionization as well as photoelectric. The ionization smoke detector uses a small amount of
radiation to ionize the air which makes it conductive, and then when the combustion particles
enter the chamber, they attach themselves to the ions and reduce the current flow which in turn
activates the alarm. As for the photoelectric detectors, when the combustion particles enter the
chamber, it obscures the photoelectric beam between the light source and the receiving element
which activates the alarm. Smoke detectors are more costly than heat detectors but are faster to
respond because smoke does not dissipate as fast as heat does.
Flame detectors are also scattered throughout the premises, they are fast with response
but have a high rate of false alarm. Also these have to be places where they can “see” the entire
room since they work on line of sight. Being blocked by stacking material will render them
useless.
Auxiliary Systems
Auxiliary services are special fire detection and alarm systems that can be designed to
perform special functions for buildings that have special requirements in the event of a possible
emergency. The Sonoma Veterans Memorial Building has several examples of auxiliary
functions in place to enhance the overall safety of the facility. There are magnetic doors with
magnetic door stoppers (see P-4), when fire alarm is activated the magnets are released to close
and seal off. This door release closes the auditorium so that smoke and/or fire door will not
spread to other parts of the building.
The heating, ventilation and air conditioning (HVAC) system will also shut down the
system’s blowers and ensure dampers are actuated when there is a fire to prevent the spread of
fire or smoke throughout other parts of the building. The duct smoke detector is equipped with
an auxiliary relay that immediately cuts power to the fan motor before significant amounts of
smoke can be distributed to hallways, the auditorium or dining areas.
When the emergency system is activated in the kitchen there is also an auxiliary function
that will shut off all gas to the entire kitchen as well as an added precautionary measure to make
sure that there are no additional hazards or explosions due to the presence of gas.
In addition to the above auxiliary systems this facility has also installed other safety
devices and equipment to enhance the overall safety of the building. There are flame retardant
curtains that line the windows and stage so that the bulk of the fabric material in the building is
not highly flammable. There are also exit signs that are powered by electricity and back up
battery in the event of a power outage and glow in the dark reflective strips that line key walk
ways to illuminate exit routes. There are several portable fire extinguishers located throughout
the building and the commercial kitchen is equipped with both a Class K and Class B,C fire
extinguisher.
Summary
Fire is one of the most serious threats to a building, with consequences that can include
harm to occupants and firefighters, damage to the structure and its contents, loss of building use,
visual harm to the streetscape, and impact on the tax base. When a fire occurs it must be
extinguished as soon as possible to prevent a major loss of property and/or life. If detection
occurs early, then a portable fire extinguisher may be very effective. However, a flaming fire
can rapidly exceed an extinguisher’s capabilities. When this happens the fire department must
apply large volumes of water to prevent complete loss. An alternative is to provide an automatic
fire suppression system that can detect the fire and start to control or even extinguish it before
the fire department arrives. This will reduce the amount of damage and recovery effort needed
to place the building back into use.
When it comes to safety and security, there is no margin for error. We covered several of
the main features of this buildings fire detection and suppression systems and can see how they
play a vital part in recognizing the early signs of a fire and in summoning aid. The Sonoma
Veterans Building is an older facility that has continually upgraded their emergency systems to
remain current with the laws and keep the occupants safe. Not only are lives saved by the
presence of fixed detection systems, but damage to property can also be limited if trained help
can be summoned as quickly as possible.
SUPPORTING DIAGRAMS
D-1: Sonoma Veterans Memorial Hall Floor Plan
D-2 Occupancy Guidelines
ROOM
CAPACITY
Assembly Seated Dining Dine/Dance
Auditorium
80’ x 55’
700 500 300 225
Dining Room
63’ x 33’
309 240 144 90
Lounge Room
45’x 19’
141 85 66 n/a
D-3 Fire ad Emergency Equipment Plan
SUPPORTING PICTURES
Please see the attached power point file for all of our supporting pictures that accompany this
report. These images will also be used in our in class presentation to give a better understanding
of the fire systems present in the Sonoma Veterans Memorial Building.
Collepals.com Plagiarism Free Papers
Are you looking for custom essay writing service or even dissertation writing services? Just request for our write my paper service, and we'll match you with the best essay writer in your subject! With an exceptional team of professional academic experts in a wide range of subjects, we can guarantee you an unrivaled quality of custom-written papers.
Get ZERO PLAGIARISM, HUMAN WRITTEN ESSAYS
Why Hire Collepals.com writers to do your paper?
Quality- We are experienced and have access to ample research materials.
We write plagiarism Free Content
Confidential- We never share or sell your personal information to third parties.
Support-Chat with us today! We are always waiting to answer all your questions.